GB/T 16895 Low-voltage electrical installations is divided into five parts, and each part is divided into several sub-parts:
——Part 1: Fundamental principles, assessment of general characteristics, definition;
——Part 4: Protection for safety;
——Part 5: Selection and erection of electrical equipment;
——Part 6: Verification;
——Part 7: Requirements for special installations or locations.
This part is sub-part 42 of GB/T 16895 Low-voltage electrical installations—Part 4: Protection for safety.
This part is developed in accordance with the rules given in GB/T 1.1-2009.
This part replaces GB/T 16895.2-2005 Electrical installations of buildings—Part 4-42: Protection for safety—Protection against thermal effects, and the following main technical changes have been made with respect to GB/T 16895.2-2005:
——The scope now includes protection against all thermal effects and flames in case of a fire hazard being propagated from electrical installations to other fire compartments segregated by barriers which are in the vicinity.
——Requirements associated with escape routes for evacuation in an emergency have been expanded/modified;
——Requirements associated with the nature of processed or stored materials have been expanded/modified;
——Requirements associated with combustible constructional materials have been expanded/modified;
——Requirements associated with fire propagating structures have been expanded/modified;
——New requirements for the selection and erection of installations in locations which might endanger precious goods have been added;
——Protection against overheating now includes space heating appliances.
This part, by means of translation, is identical to IEC 60364-4-42: 2010 Low-voltage electrical installations—Part 4-42: Protection for safety—Protection against thermal effects.
The Chinese documents identical to the normative international documents given in this part are as follows:
——GB 7000.17-2003 Safety requirements for luminaires with limited surface temperatures (IEC 60598-2-24: 1997, IDT)
——GB/T 18380 (all parts) Tests on electric and optical fiber cables under fire conditions [IEC 60332 (all parts)]
——GB/T 19215 (all parts) Cable trunking and ducting systems for electrical installations [IEC 61084 (all parts)]
——GB/T 19215 (all parts) Cable trunking and ducting systems for electrical installations [IEC 61084 (all parts)]
——GB/T 20041 (all parts) Conduit systems for cable management [IEC 61386 (all parts)]
——GB/T 21762—2008 Cable management—Cable tray systems and cable ladder systems (IEC 61537: 2006, IDT)
This part is identical to IEC 60364-4-42: 2010 in clause and article numbers and technical contents, with only the following editorial changes:
Annex A has been deleted in this part as it is the national note of other countries applying this standard and is irrelevant to China.
This standard was proposed by and is under the jurisdiction of SAC/TC 205 National Technical Committee on Electrical Installations of Buildings of Standardization Administration of China.
The previous editions of this standard are as follows:
——GB/T 16895.2-1997, GB 16895.2-2005, GB/T 16895.2-2005.
Low-voltage electrical installations—
Part 4-42: Protection for safety—Protection against thermal effects
420.1 Scope
This part of GB/T 16895 applies to electrical installations with regard to measures for the protection of persons, livestock and property against
——thermal effects, combustion or degradation of materials, and risk of burns caused by electrical equipment,
——flames in case of a fire hazard being propagated from electrical installations to other fire compartments segregated by barriers which are in the vicinity, and the impairment of the safe functioning of electrical equipment including safety services.
Note: Protection against overcurrent is dealt with in IEC 60364-4-43.
420.2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
GB/T 16895.18-2010 Electrical installations of buildings—Part 5-51: Selection and erection of electrical equipment—Common rules (IEC 60364-5-51: 2005, IDT)
GB/T 16895.21-2011 Low-voltage electrical installations—Part 4-41: Protection for safety—Protection against electric shock (IEC 60364-4-41:2005, IDT)
IEC 60332 (all parts) Tests on electric and optical fibre cables under fire conditions
IEC 60598-2-24 Luminaires Part 2-24: Particular requirements—Luminaires with limited surface temperatures
IEC 61084 (all parts) Cable trunking and ducting systems for electrical installations
IEC 61386 (all parts) Conduit systems for cable management
IEC 61534 (all parts) Powertrack systems
IEC 61537 Cable management—Cable tray systems and cable ladder systems
420.3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
420.3.1
combustible
capable of burning
420.3.2
fire
——a process of combustion characterized by the emission of heat and effluent accompanied by smoke, and/or flame and/or glowing
——rapid combustion spreading uncontrolled in time and space
420.3.3
flammability
ability of a material or product to burn with a flame under specified test conditions
420.3.4
ignitability
measure of the ease with which a specimen can be ignited due to the influence of an external source, under specified test conditions
420.3.5
ignition
initiation of combustion
Note: For more information see IEC 60695-4.
420.3.6
non-flam propagating component
component which is liable to ignite, as a result of an applied flame, but in which the flame does not propagate and which extinguishes itself within a limited time after the flame is removed
[IEC 60050-442:1998, 442-01-12]
421 Protection against fire caused by electrical equipment
421.1 General requirements
Persons, livestock and property shall be protected against damage or injury caused by heat or fire which may be generated or propagated in electrical installations by taking into account the requirements of this standard and the instructions of equipment manufacturers.
The heat generated by electrical equipment shall not cause danger or harmful effects to adjacent fixed material or to material which may foreseeably be in proximity to such equipment. Electrical equipment shall not present a fire hazard to adjacent materials.
Note: Damage, injury or ignition may be caused by effects such as
——heat accumulation, heat radiation, hot elements,
——reduction of the safe function of electrical equipment, e.g. protective devices such as protective switchgear, thermostats, temperature limiters, seals of cable penetrations and wiring systems,
——overcurrent,
——insulation faults and/or arcs causing interference,
——harmonic currents,
——lightning strikes, see the IEC 62305 series,
——overvoltage, see Clause 443 of GB/T 16895.10-2010,
——inappropriate selection or erection of equipment.
Any relevant manufacturer’s erection instructions shall be taken into account in addition to the requirements of the GB/T 16895 series.
421.2 Where fixed equipment may attain surface temperatures which could cause a fire hazard to adjacent materials, the equipment shall either
· be mounted on or within materials that will withstand such temperatures and are of low thermal conductance, or
· be screened from elements of building construction by materials which will withstand such temperatures and are of low thermal conductance, or
Foreword i
420.1 Scope
420.2 Normative references
420.3 Terms and definitions
421 Protection against fire caused by electrical equipment
422 Precautions where particular risks of fire exist
422.1 General
422.2 Conditions of evacuation in an emergency
422.3 Locations with risks of fire due to the nature of processed or stored materials
422.4 Locations with combustible constructional materials
422.5 Fire propagating structures
422.6 Selection and erection of installations in locations with endangering of irreplaceable goods
423 Protection against burns
424 Protection against overheating
424.1 Forced air heating systems
424.2 Appliances producing hot water or steam
424.3 Space heating appliances
Bibliography
ICS 91.140.50
Q 77
GB
中華人民共和國國家標準
GB/T 16895.2—2017/IEC 60364-4-42:2010
代替GB/T 16895.2—2005
________________________________________________________________________
低壓電氣裝置
第4-42部分:安全防護 熱效應保護
Low-voltage electrical installations—
Part 4-42:Protection for safety—Protection against thermal effects
(IEC 60364-4-42:2010,IDT)
2017-11-01發布 2018-05-01實施
中華人民共和國國家質量臨督檢驗檢疫總局
中國國家標準化管理委員會 發布
前言
GB/T 16895《低壓電氣裝置》共分為5個部分,每個部分又分為多個子部分:
——第1部分:基本原則、一般特性評估和定義;
——第4部分:安全防護;
——第5部分:電氣設備的選擇和安裝;
——第6部分:檢驗;
——第7部分:特殊裝置或場所的要求。
本部分為GB/T 16895《低壓電氣裝置》的第4部分:安全防護中的第42部分。
本部分按照GB/T 1.1—2009給出的規則起草。
本部分代替GB/T 16895.2—2005《建筑物電氣裝置 第4-42部分:安全防護 熱效應保護》,與GB/T 16895.2—2005相比,主要技術變化如下:
——其范圍現在包括,在電氣裝置向其臨近的其他防火分隔蔓延火災時,對其產生的所有熱效應和火焰進行防護;
——增加/修改了關于緊急情況下疏散路線的要求;
——增加/修改了關于加工的或貯存的物料件質的要求;
——增加/修改了關于可燃建筑材料的要求;
——增加/修改了關于火焰蔓延結構的要求;
——增加了可能會危及貴重物品的場所,其裝置的選擇和安裝的新要求;
——增加了過熱防護中的空間加熱設備。
本部分使用翻譯法等同采用IEC 60364-4-42:2010《低壓電氣裝置 第4-42部分:安全防護 熱效應保護》。
與本部分中規范性引用的國際文件有一致性對應關系的我國文件如下:
——GB 7000.17—2003 限制表面溫度燈具安全要求(IEC 60598-2-24:1997,IDT)
——GB/T 18380(所有部分) 電纜和光纜在火焰條件下的燃燒試驗[IEC 60332(所有部分)]
——GB/T 19215(所有部分) 電氣安裝用電纜槽管系統[IEC 61084(所有部分)]
——GB/T 19215(所有部分) 電氣安裝用電纜槽管系統[IEC 61084(所有部分)]
——GB/T 20041(所有部分) 電氣管理用導管系統[IEC 61386(所有部分)]
——GB/T 21762—2008 電纜管理 電纜托盤系統和電纜梯架系統(IEC 61537:2006,IDT)
本部分與IEC 60364-4-42:2010相比,章、條編號完全一致,技術內容完全相同,但做了以下編輯性修改:
由于附錄A是其他國家應用該標準的國家注,與我國無關,在本部分中刪去。
本部分由全國建筑物電氣裝置標準化技術委員會(SAC/TC 205)提出并歸口。
本部分所代替標準的歷次版本發布情況為:
——GB/T 16895.2—1997、GB 16895.2—2005、GB/T 16895.2—2005。
低壓電氣裝置
第4-42部分:安全防護 熱效應保護
420.1 范圍
GB/T 16895的本部分適用于涉及人、家畜和財產的電氣裝置的防護:
——電氣裝置引起的熱效應、材料燃燒或劣化以及灼傷的風險;
——發生火災時,電氣裝置內的火焰蔓延至附近的有防火分隔的防火分區;和包括安全設施的電氣設備,其安全功能的損害。
注:過電流防護在IEC 60364-4-43中進行了規定。
420.2 規范性引用文件
下列文件對于本文件的應用是必不可少的。凡是注日期的引用文件,僅注日期的版本適用于本文件,凡是不注日期的引用文件,其最新版本(包括所有的修改單)適用于本文件。
GB/T 16895.18—2010 建筑物電氣裝置 第5-51部分:電氣設備的選擇和安裝 通用規則(IEC 60364-5-51:2005,IDT)
GB/T 16895.21—2011 低壓電氣裝置 第4-41部分:安全防護 電擊防護(IEC 60364-4-41:2005,IDT)
IEC 60332(所有部分) 電纜和光纜在火焰條件下的燃燒試驗(Tests on electric and optical fibre cables under fire conditions)
IEC 60598-2-24 燈具 第2部分:特殊要求 第24章:限制表面溫度燈具(Luminaires Part 2-24:Particular requirements—Luminaires with limited surface temperatures)
IEC 61084(所有部分) 電氣安裝用電纜槽管系統(Cable trunking and ducting systems for electrical installations)
IEC 61386(所有部分) 電氣管理用導管系統(Conduit systems for cable management)
IEC 61534(所有部分) 電源軌道系統(Powertrack systems)
IEC 61537 電纜管理 電纜托盤系統和電纜梯架系統(Cable management—Cable tray systems and cable ladder systems)
420.3 術語和定義
下列術語和定義適用于本文件。
420.3.1
可燃 combustible
能夠燃燒。
420.3.2
火災 fire
——一個燃燒過程,其特點是排放熱和廢氣并伴隨濃煙,和/或火焰和/或灼熱;
——燃燒不受時間和空間控制的快速蔓延。
420.3.3
可燃性 flammability
在規定試驗條件下,材料或產品伴有火焰的燃燒能力。
420.3.4
易燃性 ignitability
在規定試驗條件下,由于外部熱源的影響,點燃樣品的難易程度。
420.3.5
起燃 ignition
開始燃燒。
注:有關更多信息,參見IEC 60695-4。
420.3.6
非火焰蔓延部件 non-flam propagating component
該部件易燃,由于其燃燒時火焰不會蔓延,并在火焰撤除后,在限定時間內會自行熄滅的部件。
[IEC 60050-442:1998,定義442-01-12]
421 電氣設備引起火災的防護
421.1 一般要求
根據本部分的要求和設備制造商的說明書,人、家畜和財產應防護由電氣裝置所產生或傳播的熱量或火災所引起的損害或傷害。
電氣設備所產生的熱量不應對相鄰固定材料或預計可能鄰近的材料產生危險或有害的影響。電氣設備不應對相鄰材料存在火災危險。
注:以下影響因素可引起損害、損傷或燃燒:
——熱聚集、熱輻射、發熱元件;
——電氣設備例如保護裝置(如保護開關設備、恒溫器、限溫器、電纜穿墻的密封和布線系統)安全功能的降低;
——過電流;
——絕緣故障和/或電弧的干擾;
——諧波電流;
——雷擊,參見IEC 62305;
——過電壓,參見GB/T 16895.10—2010的443條款;
——設備不適當的選擇或安裝。
除GB/T 16895要求外,還應考慮任何相關制造商的安裝說明。
421.2 固定設備可能達到的表面溫度,會造成相鄰材料的火災危險,設備應:
· 安裝或密封在能夠承受該溫度的材料中,且該材料具有低熱導率;或,
· 從能承受該溫度且具有低熱導率的建筑材料中篩選;或,
· 設備的安裝位置應距所有材料有足夠的距離且可安全散熱,以避免材料上的溫度產生可能有害的熱效應,且任何支撐裝置均具有低熱導率。
421.3 在正常運行條件下,如永久連接的設備可能會產生電弧或火焰,設備應:
· 完全封閉在耐弧材料中;或
· 材料有可能排放有害物質,需選用耐弧材料進行遮蔽;或
· 材料可能排放有害物質,其安裝要有足夠的距離,以便有害物安全排放。
該防護措施所使用的耐護弧材料應不可燃、低熱導率和具有足夠的厚度以提供機械穩定性。
注:例如,一個由20 mm厚的玻璃纖維硅膠制成的扳材可視為耐弧材料。
421.4 引起熱聚集的固定設備的位置應與所有固定物或建筑構件保持足夠的距離,因此,在正常運行條件下,該物體或構件不會出現危險溫度。例如,超過其起燃溫度。
注:宜考慮到設備制造商提供的所有信息。
421.5 如單獨安裝的電氣設備且有一定數量的可燃液體,應采取充足的預防措施以防止液體、火焰和燃燒產物的蔓延。
注1:此類預防措施舉例如下:
· 收集任何泄漏液體的貯留池,以確保發生火災時將其熄火;
· 將設備安裝在具有足夠的耐火等級的小室內,并設置遮擋或采取其他措施以防止燃燒的液體蔓延到建筑物的其他部位,這種小室要有通向戶外的單獨通風。
注2:通常認為一定數量的下限是25 L。
注3:對于少于25 L,采取預防措施以防止液體泄漏是非常重要。
注4:液體的燃燒產物為火焰、煙和氣。
注5:在火災開始時,需要切斷電源。
421.6 在安裝中電氣設備所采用的外護物的材料,應能承受該電氣設備可能產生的最高溫度。
可燃材料不適用于制作這類外護物,除非采取了覆蓋不燃的或難燃的低熱導率的材料等防火的措施。
422 火災特別危險的場所的防護措施
422.1 一般要求
422.1.1 電氣設備應限制其使用的場所,但按照422.3.5規定的布線系統除外。
422.1.2 電氣設備在正常使用時的溫度和故障期間可預測的溫升情況下,其選擇和安裝應確保溫度不會引起火災。
這些配置可能會受設備結構或其安裝條件的影響。
電氣設備的表面溫度不可能引燃附近物質時,其不需要特殊措施。
422.1.3 熱脫扣器件應僅用于手動復位。
422.2 緊急疏散的條件
條件分為:
BD2:低密度,疏散困難;
BD3:高密度,疏散容易;
BD4:高密度,疏散困難。
(按照GB/T 16895.18—2010中的表51A)
注:主管建筑建設,公共集會,消防等部門負責說明擬建項目是屬于上述哪一類BD條件。
422.2.1 在BD2、BD3和BD4條件下,布線系統不應占用安全通道,除非布線系統的接線具有由電纜管理系統自身或通過其他方式提供的護套或外殼。
占用安全通道的布線系統不應在伸臂范圍以內,除非設置了防止在疏散時可能出現機械損傷的保護。
安全通道內的任何布線系統應盡可能的短且應為阻燃的。
注1:使用以下產品可符合上述要求:
——電纜燃燒測試規定見IEC 60332-1-2和火災條件的規定見IEC 60332-3-21、IEC 60332-3-22、IEC 60332-3-23、IEC 60332-3-24、IEC 60332-3-25;
導管系統阻燃分類的規定見IEC 61386-1;
電纜槽盒系統阻燃分類的規定見IEC 61084-1;
——電纜托盤和電纜梯架系統阻燃分類的規定于IEC 61537;
動力軌道系統規定見IEC 61534。
在BD2、BD3和BD4條件下,為安全設施供電回路的布線系統應具有一定的耐火等級,其耐火時間等級由建筑構件的規范規定,或如其無規定則取為1 h。
注2:對于火災條件下,安全設施布線系統的功能要求,參見IEC 60364-5-56。
安全通道中的布線系統應限制煙氣的產出率。
注3:如電纜標準未提供任何詳細規定,那么建議60%的透光率可被采納,作為IEC 61034-2測試任何電纜的最低限度。
422.2.2 在BD2、BD3和BD4條件下,除用于便利疏散的某些裝置以外,開關設備和控制設備只有規定的人員才能接近。如果這些開關設備和控制設備被裝在通道內,則應將他們裝在不燃的或難燃的材料制作的柜子或箱子內。
注:本條款并不禁止使用不可燃的塑料外殼。
422.2.3 在BD3、BD4條件下和在安全通道內,禁止使用有可燃液體的電氣設備。
注:組裝在設備中的個別輔助電容器不必滿足本要求。這種例外主要指氣體放電燈和電動機起動器的電容器。
422.3 因加工的或貯存的物料的性質而引發火災危險的場所
BE2條件:火災危險(按照GB/T 16895.18 2010的表51A)。
注:關于爆炸危險,見IEC 60079-14。
422.3.1 燈具應與可燃材料保持足夠距離。如果制造商沒有提供其他信息,那么聚光燈和投影儀應在距可燃材料以下最小距離進行安裝:
≤100 W 0.5 m
>100 W~300 W 0.8 m
>300 W~500 W 1.0 m
>500 W 更遠距離可能是必要的。
注:如制造商說明書中未作規定,上述距離意味著各個方向。
燈具和其他組件應防止可預見的機械應力。此類防護措施不應安裝在燈座上,除非他們是燈具的組成部分。不容許對燈具進行修改。
根據制造商說明書的要求,帶燈泡(該燈泡在故障情況下可能會噴出易燃材料)的燈具應為燈泡配備安全防護罩。
注:根據IEC 60598-1:2003(第六版)要求,可安裝在可燃物表面的燈具,有如下標記。
已出版的IEC 60598-1:20081)的規定,沒有特殊標標記的燈具可直接安裝在可燃物表面但是不適合直接安裝在可燃物表面的燈具,有如下標記。(詳細內容參見IEC 60598-1:2008的N.4)
和/或
_____________
1) 該第七版撤銷并替代了第六版。
422.3.2 應采取措施以防止電氣設備(如加熱器或電阻器)的外殼溫度超過以下溫度:
——正常條件下為90℃;且
——故障情況下為115℃。
如果足以引起火災危險的材料(如:粉塵或纖維)可能會聚集在電氣設備的外殼上,應采取有效的措施防止外殼溫度超過上述溫度。
注:按照IEC 60598-2-24要求,標有 標志的燈具設計要提供表面限制溫度。
422.3.3 用于保護、控制和隔離的開關裝置應放置于BE2條件場所之外,除非將他們放置在外殼內,在該場所內的外殼需提供一定程度的保護,至少是IP4X防護等級或,如存在灰塵應選用IP5X防護等級或,如存在導電粉塵應選用IP6X防護等級,除非符合422.3.11的規定。
422.3.4 除非線路和布線系統敷設于不可燃材料中,否則僅可使用阻燃的布線系統。
至少應根據以下要求選擇設備:
——電纜應滿足IEC 60332中規定的火焰條件下的燃燒試驗的要求;
——導管系統應滿足IEC 61386中規定的阻燃試驗的要求;
——電纜槽盒系統和電纜管道系統應滿足IEC 61084中規定的阻燃試驗的要求;
——電纜托盤系統和電纜梯架系統應滿足IEC 61537中規定的阻燃試驗的要求;
——動力軌道系統應滿足IEC 61534中規定的阻燃試驗的要求。
注1:如果火焰蔓延風險高,當長而且垂直成束的電纜運行時,電纜宜滿足IEC 60332-3中適用部分的蔓延特性。
注2:電纜管理系統的燃燒試驗總是在垂直構造中進行。
422.3.5 布線系統橫穿這些場所,但不用于這些場所時應滿足以下條件:
· 布線系統應滿足422.3.4的規定;
· 布線系統在這些場所不得有接頭,除非這些連接均密封在耐火外殼中;
· 按照422.3.10的規定,防止布線系統出現過電流;
· 不應使用裸導體。
422.3.6 在強制排熱風裝置中,進氣口應位于可能出現可燃粉塵的場所外。
排氣溫度不應對該場所帶來火災危險。
422.3.7 自動、遙控或沒有持續監控的電動機,應設置溫度傳感器防止溫度過高,除非在其內部特別設計了限熱保護。
422.3.8 每個燈具應:
· 適合的安裝位置,且
· 配備外殼,該外殼至少是IP4X的防護等級,或有灰塵環境,采用IP5X的防護等級或,有導電性粉塵環境,提供IP6X的防護等級,且
· 按照IEC 60598-2-24要求,其表面有溫度的限制,且
· 其類型應可防止燈泡部件從燈具上掉落。
由于在粉塵或纖維的場所可能會現火災危險,所安裝的燈具應使粉塵或纖維無法聚集到危險的數量。
注:燈具也需符合IEC 60598系列的相關要求。也可參見IEC 60364-5-55:2001的559。
422.3.9 應對終端回路和用電設備進行保護以防出現以下的絕緣故障:
a) 在TN和TT系統中,剩余電流保護器的額定動作電流應為I△n≤300 mA。如電阻性故障可引起火災(例如天花板采暖用電熱膜元件),額定剩余動作電流應為I△n≤30 mA;
b) 在IT系統中,應提供監測所有裝置的絕緣監測設備或裝設在終端電路中的RCMs(剩余電流監測裝置),且均具有聲光信號。或者,可使用a)中指定的額定動作電流的剩余電流保護器(RCD)。在第二次故障發生時,參見IEC 60364-4-41部分的斷開時間。
礦物絕緣電纜和母線槽系統不考慮由絕緣故障而引起的火災,因此不需要保護。
注:推薦使用具有金屬保護層的電纜。金屬保護層宜連接至保護導體。
422.3.10 直接供電或穿過BD2條件的場所的回路應防止其過負荷和短路,其保護裝置是位于BD2場所的外部和電源側,應在BD2場所內的回路起始點設置過電流保護裝置。
422.3.11 在SELV或PELV供電回路中,帶電部分應:
· 密封在IP2X或IPXX B防護等級的外殼中,或
· 配備能承受1 min直流500 V試驗電壓的絕緣材料。
無論回路標稱電壓的數值,其還應符合GB 16895.21—2011的414.4.5的要求。
422.3.12 在BE2條件的場所不允許使用PEN導體,除非是貫穿該場所的回路,且該回路的PEN導體與該場所內的任何導電部分應無任何連接。
422.3.13 在BE2條件的場所,每個用電設備的供電回路應提供所有帶電導體的隔離措施,因此當一個或多個帶電導體斷開,回路的非帶電導體要保持閉合導通,這是可以通過機械聯鎖開關或機械聯鎖斷路器來實現。
注:如果供電條件允許,可采用一個隔離元件隔離一組回路。
422.4 具有可燃建筑材料的場所
CA2條件:可燃(參照GB/T 16895.18—2010的表51A)。
422.4.1 應采取預防措施以確保電氣設備不會使墻壁、地板或天花板引起火災。這可通過合理的設計及電氣設備的選擇和安裝來實現。
電氣設備的接線盒和外殼安裝在預制空心墻內時,為了避免鉆入固體異物,至少應具有IP3X防護等級。
422.4.2 燈具應與可燃材料保持足夠距離。如果制造商沒有提供其他信息,那么聚光燈和投影儀應在
距可燃材料以下最小距離進行安裝:
≤100 W 0.5 m
>100 W~300 W 0.8 m
>300 W~500 W 1.0 m
>500 W 更遠距離可能是必要的。
注:如制造商說明書中未作規定,上述距離意味著各個方向。
燈具和其他組件應防止可預見的機械應力。此類防護措施不應安裝在燈座上,除非他們是燈具的組成部分。
根據制造商說明書的要求,帶燈泡(該燈泡在故障情況下可能會噴出易燃材料)的燈具應為燈泡配備安全防護罩。
注:根據IEC 60598-1:2003(第六版)要求,可安裝在可燃物表面的燈具,有如下標記。
已出版的IEC 60598-1:2008規定,沒有特殊標記的燈具可直接安裝在可燃物表面但是不適合直接安裝在可燃物表面的燈具,有如下標記。(洋細內容參見IEC 60598-1:2008的N.4)
和/或
422.5 火災可蔓延的結構
條件CB2:火災的蔓延(根據GB/T 16895.18—2010的表51A)。
422.5.1 對于形狀和大小會助長火災蔓延的結構,應采取預防措施以確保電氣裝置不會蔓延火災(例如煙囪效應)。
注:可裝設火災探測器防止火災蔓延.例如管道、建筑孔洞、洞的防火閥(門)的關閉等。符合IEC 60670-1的接線盒和外殼可用于空心墻內和符合IEC 60332-3電纜可被使用。IEC 60670-1中標記H的接線盒和外殼可用于空心墻內。
422.6 危及不可替代物品的場所內電氣裝置的選擇和安裝
應滿足422.1.2的要求。
注1:包括具有重要價值的建筑物或房屋的場所。
例如:國家歷史文物、博物館和其他公共建筑。如:火車站和機場,建筑或設施如:實驗室、計算機中心和某些工業和倉儲設施。
注2:可考慮以下措施:
——根據IEC 60702-1要求,敷設礦物絕緣電纜;
——如果發生火災危險,敷設具有提高耐火特性的電纜,且符合IEC 60331-1或IEC 60331-21或類似的規定;
——在非可燃實體墻、天花板和地板中敷設電纜;
——在具有30 min或90 min耐火性能的建筑分區中敷設電纜,后者的場所是指住宅樓梯和緊急疏散通道。
如這些措施不可行,可通過使消防滅火系統加強防護。
423 灼傷防護
在伸臂范圍內的電氣設備,其可接近部分的溫度不應達到可能造成人員灼傷的程度,并且應遵守表42.1所列的相應溫度限值的規定。在正常工作中,裝置的所有部分即使是短時間的,其溫度可能出現超過表42.1所列限值時,應加以防護,防止任何意外接觸。表42.1中的值不適用于已符合國家標準的某些設備。
注:如符合條件BA2(兒童),較低的溫度可能是可行的。
表42.1 伸臂范圍內設備的可觸及部分正常工作時的溫度限值
可觸及部分 可觸及表面的材料 最高溫度
℃
操作時手握的部分 金屬的
非金屬的 55
65
有意觸及的,但非手握的部分 金屬的
非金屬的 70
80
正常操作時不必觸及的部分 金屬的
非金屬的 80
90
424 過熱防護
424.1 強迫通風加熱系統
強迫通風加熱系統的加熱元件,除中央蓄熱器外,其加熱元件直到產生了規定的氣流量才會被起動,且當氣流量少于規定值時不能起動。另外,應設置兩個獨立的限溫器件,可防止通風管道中的溫度超過允許值。
加熱元件的支撐零件、框架和外殼應均為非可燃性材料。
424.2 產生熱水或蒸汽的設備
所行產生熱水或蒸汽的設備在各種工作狀態下都應被保護,設計或安裝都不應導致其過熱。除非這些設備完全符合相應國家標準的規定,否則應采用一種適當的非自動復位式元件來保護,該元件的工作與設備的溫度控制器無關。
如果這類設備沒有溢出口,還應有限制水壓的器件。
424.3 空間加熱設備
空間加熱設備的框架和外殼應為非可燃性材料。
注:在有火災危險的工作區域,如果空氣是從這些工作區域引至設備,那么空間加熱設備不能運行。
熱輻射中不能觸摸的輻射加熱器,其側置應與可燃零件保持足夠的距離。當設置不可燃隔板使分隔距離減少時,該隔板與輻射加熱器的外殼以及可燃零件的距離至少應為1 cm。除非制造商另行規定,安裝輻射加熱器并確保熱輻射方向與易燃零件的安全距離宜至少為2 m。
參考文獻
[1] GB/T 2900.70—2008 電工術語 電器附件(IEC 60050-442:1998,IDT)
[2] GB 3836.15—2000 爆炸性氣體環境用電氣設備 第15部分:危險場所電氣安裝(煤礦除外)(eqv IEC 60079-14:1996)
[3] GB/T 16895.10—2010 低壓電氣裝置 第4-44部分:安全防護 電壓騷擾和電磁騷擾防護(IEC 60364-4-44:2007,IDT)
[4] GB/T 18380.12—2008 電纜和光纜在火焰條件下的燃燒試驗 第12部分:單根絕緣電線電纜火焰垂直蔓延試驗 1 kW預混合型火焰試驗方法(IEC 60332-1-2:2004,IDT)
[5] GB/T 18380.32—2008 電纜和光纜在火焰條件下的燃燒試驗 第32部分:垂直安裝的成束電線電纜火焰垂直蔓延試驗 A F/R類(IEC 60332-3-21:2000,IDT)
[6] GB/T 18380.33—2008 電纜和光纜在火焰條件下的燃燒試驗 第33部分:垂直安裝的成束電線電纜火焰垂直蔓延試驗 A類(IEC 60332-3-22:2000,IDT)
[7] GB/T 18380.34—2008 電纜和光纜在火焰條件下的燃燒試驗 第34部分:垂直安裝的成束線電纜火焰垂直蔓延試驗 B類(IEC 60332-3-23:2000,IDT)
[8] GB/T 18380.35—2008 電纜和光纜在火焰條件下的燃燒試驗 第35部分:垂直安裝的成束電線電纜火焰垂直蔓延試驗 C類(IEC 60332-3-24:2000,IDT)
[9] GB/T 18380.36—2008 電纜和光纜在火焰條件下的燃燒試驗 第36部分:垂直安裝的成束電線電纜火焰垂直蔓延試驗 D類(IEC 60332-3-25:2000,IDT)
[10] IEC 60331-1 Tests for electric cables under fire conditions—Circuit integrity—Part 1:Test method for fire with shock at a temperature of at least 830℃ for cables of rated voltage up to and including 0.6/1.0 kV and with an overall diameter exceeding 20 mm
[11] IEC 60331-21 Tests for electric cables under fire conditions Circuit integrity Part 21:Procedures and requirements—Cables of rated voltage up to and including 0.6/1.0 kV
[12] IEC 60364-4-43 Low—voltage electrical installations—Part 4-43:Protection for safety—Protection against overcurrent
[13] IEC 60364-5-52 Low-voltage electrical installations—Part 5-52:Selection and erection of electrical equipment—Wiring systems
[14] IEC 60364-5-55:2001 Electrical installations of buildings—Part 5-55:Selection and erection of electrical equipment—Other equipment
[15] IEC 60364-7-753 Low-voltage electrical installations Part 7-753:Requirements for special installations or locations—Floor and ceiling heating systems
[16] IEC 60598 (all parts) Luminaires
[17] IEC 60598-1:2003 Luminaires—Part 1:General requirements and tests
[18] IEC 60598-1:2008 Luminaires—Part 1:General requirements and tests
[19] IEC 60670-1 Boxes and enclosures for electrical accessories for household and similar fixed electrical installations—Part 1:General requirements
[20] IEC 60695-4 Fire hazard testing—Part 4:Terminology concerning fire tests for electro-technical products
[21] IEC 60702-1 Mineral insulated cables and their terminations with a rated voltage not exceeding 750 V—Part 1:Cables
[22] IEC 60947-2 Low-voltage switchgear and controlgear—Part 2:Circuit-breakers
[23] IEC 61034-2 Measurement of smoke density of cables burning under defined conditions—Part 2:Test procedure and requirements
[24] IEC 61084-1 Cable trunking and ducting systems for electrical installations—part 1:General requirements
[25] IEC 61386-1 Conduit systems for cable management—Part 1:General requirements
[26] IEC 61439-1 Low—voltage switchgear and controlgear assemblies—Part 1:General rules
[27] IEC 62020 Electrical accessories—Residual current monitors for household and similar uses (RCMs)
[28] IEC 62305 (all parts) Protection against lightning